Guangzhou Yike New Energy Technology Co., Ltd. was founded in 2011, is a research and development, independent innovation, production, sales as one of the modern science and technology enterprises, has been committed to manufacturing and sales of heat pump drying dehumidifier, central air conditioning, heat pump water heater and other products.
Through years of research and development and practical experience, the core products of heat pump drying dehumidifier have formed five series of heat pump drying dehumidifier: (1) wood drying special heat pump drying dehumidifier. (2), agricultural products special heat pump drying dehumidifier. (3) Seafood, fish special heat pump drying dehumidifier. (4) Special heat pump drying and dehumidifying machine for production line. (5) Chinese herbal medicine special heat pump drying dehumidifier. The products are sold all over the country and are well received by new and old customers at home and abroad.
ECOZ air source heating heat pump is a new type, energy-saving and environment-friendly constant temperature indoor heating system, including three parts: heat source, conveying pipeline and control system. It can provide heating for community houses, apartment buildings, villas, office buildings, hotels, hospitals, public bathrooms, indoor swimming pools and other buildings around the clock.
ECOZ heating heat pump can be used for many purposes in a building. It can be directly connected to various terminals, including fan coil, radiator, floor heating, etc., and it is more flexible to use with it. Apart from heating and cooling, ECOZ heat pump can also be connected to the hot water system in the building, realizing the integration of 24-hour hot water, cooling in summer and heating in winter.
There is no sense of hot air, the air is not dusty, more comfortable, less dry, so that you are away from air conditioning disease, no pollution, no burning effluents, environmental protection and clean.
1. The unit is equipped with intelligent defrost function and intelligent induction automatic defrosting, which effectively solves the situation that the unit cannot start due to cold frosting.
2. The use of high-quality spare parts effectively reduces the probability of frost formation and ensures the smooth operation of the unit in cold environments.
3. Microcomputer automatic control,double automatic control, automatic circulation heating, not subject to weather conditions, can run every day all year round, no need for personal care.
4. Using environmentally friendly refrigerant, driven by only a small amount of electrical energy, low energy consumption, no pollutant emissions during the operation of the heat pump unit.
Well-known brand jet enthalpy compressor (the latest generation of scroll compressor technology), higher heating energy efficiency ratio: new economy, chassis heating belt, crankshaft heating belt configuration, low temperature heat pump defrosting system, "dual core power" ultra-low temperature rapid heating, to ensure stable operation of the unit in a low temperature environment of -35℃; Water and electricity separation, pipe buried in the ground, no scaling no corrosion; All-weather intelligent operation, can set automatic switch time.
Model | KCL-05RL | KCL-10RL | KCL-15RL | KCL-25RL | KCL-50RL |
Refrigeration capacity(kW) | 13.5 | 27 | 34.5 | 60 | 120 |
Heating capacity(kW)(kW) | 18.4 | 36.8 | 46.2 | 80 | 161.2 |
Input power(kW) | 4.9 | 9.8 | 11.7 | 21.4 | 41.6 |
Working Voltage | 380v/3ph/50Hz | 380v/3ph/50Hz | 380v/3ph/50Hz | 380v/3ph/50Hz | 380v/3ph/50Hz |
Operation control | Microcomputer automatic control, operating status display, abnormal state alarm | ||||
Safety devices | High and low voltage switch, anti-freezing swi tch, overcurrent protection switch, phase sequence protector, compressor overheat protection device | ||||
External fan air volume(m³/h) | 3000 | 6000 | 13000 | 20000 | 40000 |
External fan power(kW) | 0.25(kW) | 0.5(kW) | 0.75(kW) | 1.5(kW)×2 | 1.5(kW)×2 |
Noise(dB) | 《52 | 《55 | 《56 | 《65 | 《70 |
Compressor type | Scroll type | Scroll type | Scroll type | Scroll type | Scroll type |
Water-side heat exchanger | High-efficiency tank/plate exchange type | High-efficiency tank type/shell and tube type | |||
Water flow rate(m³/h) | 6 | 8 | 16 | 16 | 56 |
Water-resistance loss | 16 | 7 | 11 | 18 | 35 |
Inlet and outlet pipe diameter | DN25 | DN32 | DN32 | DN65 | DN100 |
Refrigerant | R410A | ||||
Number of compressors | 1 | 1 | 1 | 1 | 4 |
Working Temperature | ‘-25℃—45℃ | ||||
Dimension of the main machine(mm)(mm) | 1165.5*425.5*1216 | 1430*720.5*1069 | 1039.5*1039.5*1799 | 1039.5*1039.5*1999 | 2155*1100*2060 |
Weight(kg) | 145 | 310 | 380 | 510 | 2000 |