Air source heat pump is a kind of energy-saving device that can make the heat flow from the low heat source air to the high heat source. It is a form of heat pump. As the name suggests, the heat pump is like a pump, which can convert the low heat energy that can not be directly used into the high heat energy that can be used, so as to achieve the purpose of saving part of the high energy.
ECOZ air source heating heat pump is a new type, energy-saving and environment-friendly constant temperature indoor heating system, including three parts: heat source, conveying pipeline and control system. It can provide heating for community houses, apartment buildings, villas, office buildings, hotels, hospitals, public bathrooms, indoor swimming pools and other buildings around the clock.
60℃ outlet temperature, suitable for a variety of ends
The maximum outlet temperature is up to 60℃. According to the needs of the application site, it can be flexibly adapted to the floor heating coil radiator, open mounted fan coil, hidden fan coil, vertical fan coil, etc., which makes the installation and use more flexible.
ECOZ heating heat pump can be used for many purposes in a building. It can be directly connected to various terminals, including fan coil, radiator, floor heating, etc., and it is more flexible to use with it. Apart from heating and cooling, ECOZ heat pump can also be connected to the hot water system in the building, realizing the integration of 24-hour hot water, cooling in summer and heating in winter.
1.The unit is equipped with intelligent defrost function and intelligent induction automatic defrosting, which effectively solves the situation that the unit cannot start due to cold frosting.
2.The use of high-quality spare parts effectively reduces the probability of frost formation and ensures the smooth operation of the unit in cold environments.
3.Microcomputer automatic control,double automatic control, automatic circulation heating, not subject to weather conditions, can run every day all year round, no need for personal care.
4.Green and environmentally friendly, driven by only a small amount of electrical energy, low energy consumption, no pollutant emissions during the operation of the heat pump unit.
5. Intelligent low temperature heat pump to achieve cold winter heating is not limited by low temperature building durable, long life.
6. Heating + cooling double jet enthalpy double jet enthalpy technology.Improve the energy efficiency of heating and cooling to achieve energy saving.
For all walks of life heating + hot water
Office buildings, large shopping malls, libraries, agricultural greenhouses heating & refrigeration Central air conditioning series Schools, hospitals, hotel clubs, villas, residential buildings & refrigeration, heating, hot water heat pump series bath center, constant temperature swimming pool, hair salon, district central heating, food processing, commercial hot water series animal husbandry, agricultural aquaculture, aquaculture
Model | KCL-05RL | KCL-10RL | KCL-15RL | KCL-25RL | KCL-50RL |
Refrigeration capacity(kW) | 13.5 | 27 | 34.5 | 60 | 120 |
Heating capacity(kW)(kW) | 18.4 | 36.8 | 46.2 | 80 | 161.2 |
Input power(kW) | 4.9 | 9.8 | 11.7 | 21.4 | 41.6 |
Working Voltage | 380v/3ph/50Hz | 380v/3ph/50Hz | 380v/3ph/50Hz | 380v/3ph/50Hz | 380v/3ph/50Hz |
Operation control | Microcomputer automatic control, operating status display, abnormal state alarm | ||||
Safety devices | High and low voltage switch, anti-freezing swi tch, overcurrent protection switch, phase sequence protector, compressor overheat protection device | ||||
External fan air volume(m³/h) | 3000 | 6000 | 13000 | 20000 | 40000 |
External fan power(kW) | 0.25(kW) | 0.5(kW) | 0.75(kW) | 1.5(kW)×2 | 1.5(kW)×2 |
Noise(dB) | 《52 | 《55 | 《56 | 《65 | 《70 |
Compressor type | Scroll type | Scroll type | Scroll type | Scroll type | Scroll type |
Water-side heat exchanger | High-efficiency tank/plate exchange type | High-efficiency tank type/shell and tube type | |||
Water flow rate(m³/h) | 6 | 8 | 16 | 16 | 56 |
Water-resistance loss | 16 | 7 | 11 | 18 | 35 |
Inlet and outlet pipe diameter | DN25 | DN32 | DN32 | DN65 | DN100 |
Refrigerant | R410A | ||||
Number of compressors | 1 | 1 | 1 | 1 | 4 |
Working Temperature | ‘-25℃—45℃ | ||||
Dimension of the main machine(mm)(mm) | 1165.5*425.5*1216 | 1430*720.5*1069 | 1039.5*1039.5*1799 | 1039.5*1039.5*1999 | 2155*1100*2060 |
Weight(kg) | 145 | 310 | 380 | 510 | 2000 |